Description
| Specifications
Product Glance | Value |
Model | DCRACK |
Version | V1 |
Capacity | 47U |
Maximum load,kW | 36 |
PUE@25℃ ambient, 25℃ air supply(1-1) | 1.17 |
Supply air temperature for classic server, ℃ | 18~27℃ |
Detailed Characteristics | Value |
Part 1: Server Cabinet | Value |
Hardware Configuration | |
Size (Length*Width*Height), mm (without package) | 1,600*1,200*2,350 |
Size (Length*Width*Height), mm (with package) | 1,720*1,300*2,400 |
Net weight, kg (without package) | 668 |
Gross weight, kg (with package) | 686 |
Network connection mode | RJ45 Ethernet 10/100M |
Power Supply | |
Power supply AC Input voltage, Volt(2-1) | 380~415 AC |
Power supply AC Input Frequency Range, Hz | 50~60 |
Maximum Power supply AC Input current, Amp(2-2) | 63 |
Fan | |
Rated power, W | 2,500 |
Noise, dBA@1m | 85 |
Size (Length*Width* Thickness), mm | 378*378*375 |
Number of fans | 3 |
Part 2: External Cooler | Value |
Hardware Configuration | |
Size (Length*Width*Height), mm (without package) | 1,896*1,026*2,180 |
Size (Length*Width*Height), mm (with package) | 2,000*1,130*2,360 |
Net weight, kg (without package) | 396 |
Gross weight, kg (with package) | 414 |
Power Supply | |
Power supply AC Input voltage, Volt(2-1) | 380~415V AC |
Power supply AC Input Frequency Range, Hz | 50~60 |
Maximum Power supply AC Input current, Amp(2-2) | 63 |
Heat pump | |
Rated power, kW | 8.5 |
COP (typical) | 4.75 |
Refrigerant | R410A |
Fan | |
Rated power, kW | 1.85 |
Noise, dBA@1m | 82 |
Size (Length*Width* Thickness), mm | 805*805*211 |
Number of fans | 2 |
Refrigerant pump | |
Rated power, W | 550 |
Flow rate, m3/h | 1 |
Pump head, m | 48 |
Size (Length*Width* Height), mm | 420*152*202 |
Environment requirements | Value |
Ambient temperature, °C | -20~45℃ |
Installation distance (max), m(2-3) | 50 |
Storage temperature, °C | -20~70 |
Operation humidity(non-condensing), RH | 10~90% |
Notes:
(1-1) The typical PUE is tested at 25℃ ambient and 25 ℃ air supply, without water curtain.
(2-1) Caution: Wrong input voltage may cause server damaged.
(2-2) Three-phase AC input.
(2-3) The distance between server cabinet and external cooler.
| Purchasing Guidelines
1. The pictures shown are for reference only; the final shipment version shall prevail.
2. Contact Customer Service Robot to review the shipping cost.
| Shipping Details
1. Shipments will be scheduled on a first-paid-first-ship basis for orders on which hiveiris has received full payment.
2. You are responsible for any customs delays or returned shipments due to a lack of proper documentation. It’s highly recommended to be aware of local customs clearance policies and prepare all customs documentation ahead of time to avoid delays or unexpected costs.
3. Click here to download Certificates of Conformity and find additional information on customs clearance for hiveiris products.
| Warranty
1. A 365-day warranty period is provided starting from the shipping date. hiveiris will cover shipping costs when shipping a replacement unit within the warranty period.
2. The warranty only applies to the original purchaser who purchased the machine directly from hiveiris . Once the miner is resold, warranty coverage becomes the responsibility of the re-seller.
3. If the user fails to use the product per the given instructions, specifications, and conditions provided or changes the function settings of the unit without hiveiris ‘s prior consent, hiveiris will not be liable for any damage arising therefrom.